Detailed Rules for Battery
Maintenance
(Maintenance Rules For Valve-Regulated Sealed Lead Acid Battery
UXL Series)

一、 Requirements for Battery Room
Battery is required to be set up away from places susceptible for
suffering sparks, e.g., transformer, power switch and fuse. Safe
distance is longer than 0.5m. Indoor temperature should be about
25℃. Battery should be free from direct sunlight. The room is required
to be free from organic solvents and erosive gases. Surface and
plate of the battery are required to keep clean and free of rust.
For telephone exchange use, independent room for battery is required.
Routine examinations include the following:
1. Terminal voltage
2. Detecting for loosing, heating and erosion (clean up in time
to free from rust) in linking places.
3. Leaking and deforming at shell
4. Acid fog (frosting) around electrode pole and safe valve
二、 First-Time Use
Before use, it is not necessary to give the sealed battery an initial
charge, except for a boost charge. The latter applies a method of
current-limiting constant voltage charge. Charge voltage should
abide by specifications in The Guide Book. In normal situation (storage
time of battery is shorter than a half year at a temperature of
25℃), voltage and time for boost charge are as below:
|
Single-cell battery voltage (V)
|
Charge duration (H)
|
|
2.23
|
2~3天
|
|
2.30~2.33V
|
1~2天
|
Duration of charge varies depending on variable temperatures,
e.g., under an ambient temperature of 10-20℃, duration of charge
is required to be doubled, while under an ambient temperature higher
than 25℃, duration is required to be curtailed.
三、Floating Charge Voltage
Under an ambient temperature of 20-29℃,average floating charge
voltage is 2.23V each single-cell. Floating charge voltage varies
subject to temperature scopes as following:
|
Ambient temperature(℃)
|
Floating charge voltage(V)
|
|
0~9
|
2.29
|
|
10~19
|
2.26
|
|
20~29
|
2.23
|
|
30~39
|
2.20
|
四、 Equalizing Charge Voltage
Yuasa Battery sets 2.30~2.33V/cell as its equalizing charge voltage.
Detailed rules include the following:
1. One or more cells show a floating voltage lower than 2.18V/cell:
after discharging 50% capacity, charge for 2-3 days under manual
equalizing charge. If restoration is still unavailable, contact
us.
2. When over 20% rated capacity has been discharged, automatic equalizing
charge is needed.
3. Charge once under automatic equalizing charge every 10 weeks.
4. Time for automatic equalizing charge is 15h.
五、 Others
1. Once the battery has discharged, recharge is required to be
done at once lest unable to restore capacity due to too-long interval.
2. Avoid over-big or over-small discharge current, and discharge
voltage is required to be higher than final voltage of the battery
lest over-deep discharge occurs.
3. Do not open battery's safe valve when it is in normal use, otherwise
the battery will become less secure.
4. When assemble or disassemble the battery with series or parallel
method, to avoid short circuit, tools must be of insulation materials,
and linking bolt must be screwed tight.
5. Batteries with lower than 80% rated capacity should be replaced.