No.
|
Content |
Period
|
|
1
|
Overall Clean |
Monthly
|
|
2
|
Measuring floating charge voltage of single cell |
Monthly
|
|
3
|
Examination of appearance and liquid leaking |
Monthly
|
|
4
|
Examination of Function-setting for equalizing
charge (subject to type of battery) |
Quarterly
|
|
5
|
Discharge test (30%) for checking and measuring
single cell voltage |
Yearly
|
|
6
|
Examination of situation of contact and erosion
on leading wire and terminal |
Yearly
|
|
7
|
Examination of tightness of bolt linking single
cells |
Yearly
|