(Maintenance Rules For Valve-Regulated Sealed Lead Acid Battery NP Series)

1. Under floating charge, charge is required with fixed voltage valuing 2.275V/single cell (provided at 25¡æ). Provided the temperature is lower than 0¡æ or higher than 40¡æ, it is necessary to vary the charge voltage -3mv/single cell every 1¡æ, beginning at voltage of 25¡æ.

2. Under cycling charge, charge is required with fixed voltage valuing 2.40~2.50V /single cell (provided at 25¡æ). Provided the temperature is lower than 5¡æ or higher than 35¡æ, it is necessary to vary the charge voltage -4mv/single cell every 1¡æ, beginning at voltage of 25¡æ.
Early-stage charge current is required to be lower than 0.25CA.

Volume of charge is set 100~120% of that volume of discharge. If ambient temperature is lower than 5¡æ, the counterpart is 120~130%.

Lower temperature (lower than 5¡æ ) demands longer charge time, and higher temperature (higher than 35¡æ) disposes over-charge. Hence, 5¡æ-30¡æ is an ideal range for charge under cycling use.

To avoid over-charge, setting up a charge-timer is recommendable, or adapt charge method to automatic trickle charge.

Temperature of the battery undergoing charge is required to range between -15¡æ~+50¡æ.