(Maintenance Rules For Valve-Regulated Sealed Lead Acid Battery NP Series)

1. Temperature of battery undergoing discharge ranges between -15¡æ~+50¡æ.

2. Continuing discharge current is required to lower than 3CA ( H is required to lower than 6CA).

Allowed maximum current for variable terminals:

Types and maximum current of terminals:
Terminals
Allowed maximum current (A)
Continuing
Within 1 hour
Within 1 minute
Socket-connector terminal
187 Series
16
24
48
250 Series
25
83
75
reed terminal (0.5mm)
7
20
30

3. Final voltage of discharge varies depending on changes of current as below. Notice voltage is required not to lower than voltages below:

Discharge current and final discharge voltage discharge current:
discharge current
final discharge voltage
Below 0.2CA
1.75V/single cell
Between 0.2CA and 0.5CA
1.70V/single cell
Between 0.5CA and 1.0CA
1.55V/single cell
Above 1.0CA
1.30V/single cell

4. Charge at once after discharge. Over-charge also demands immediate charge.