Discharge
(Maintenance Rules For Valve-Regulated Sealed Lead Acid Battery
NP Series)

1. Temperature of battery undergoing discharge ranges between -15¡æ~+50¡æ.
2. Continuing discharge current is required to lower than 3CA (
H is required to lower than 6CA).
Allowed maximum current for variable terminals:
Types and maximum current of terminals:
|
Terminals
|
Allowed maximum current (A)
|
|
Continuing
|
Within 1 hour
|
Within 1 minute
|
|
Socket-connector terminal
|
187 Series
|
16
|
24
|
48
|
|
250 Series
|
25
|
83
|
75
|
|
reed terminal (0.5mm)
|
7
|
20
|
30
|
3. Final voltage of discharge varies depending on changes of current
as below. Notice voltage is required not to lower than voltages
below:
Discharge current and final discharge voltage discharge current:
|
discharge current
|
final discharge voltage
|
|
Below 0.2CA
|
1.75V/single cell
|
|
Between 0.2CA and 0.5CA
|
1.70V/single cell
|
|
Between 0.5CA and 1.0CA
|
1.55V/single cell
|
|
Above 1.0CA
|
1.30V/single cell
|
4. Charge at once after discharge. Over-charge also demands immediate
charge.