(Regulations for Maintenance of Valve-control Sealed Lead-acid Battery)

(1) In storage, the ambient temperature shall no exceed the scope of -20¡æ¡«+50¡æ.

(2) In storage of NP battery, the battery shall be fully charged. If partial content is lost during the transportation or from self-discharging, recharge before application.

(3) For long-term storage, in order to offset the self discharge, recharge the battery. The methods of recharging are as indicated in the following table:

Storage Temperature and Interval of Recharging
Storage Temperature
Interval of Recharging
Recharging Methods (by example)
Below 25¡æ one times/six months
  • For 0.25CA and 2.275V/(single grid), charge 2~3 days under fixed voltage and current.
  • For 0.25CA and 2.4V/(single grid), charge 10~16 hours under fixed voltage and current.
  • For 0.1CA, charge 8~10 hours under fixed voltage and current.
Below 30¡æ one times/four months
Below 35¡æ one times/three months
Below 40¡æ one times/two months
Storage under temperature over 40¡æ will cause bad influence on battery, which shall be avoided.

(4) Store in dry, low temperature and well-ventilated place.

(5) As deterioration of NP battery may appear in the process of storage, so it shall be applied as early as possible.

(6) If the battery is damped in storage or in transportation, the carton shall be removed immediately, so as to avoid the wet carton becoming conductor to cause battery discharge or burning of positive terminal.