Other
(Regulations for Maintenance of Valve-control Sealed Lead-acid
Battery)

(1) In using the socket joint battery, it is recommended to use
the jack type wire for connection. If searing-iron welding is necessary,
complete welding with 60W searing-iron in 5 seconds.
(2) In using the converter like UPS, avoid countercurrent from
the converter. Special attention shall be given to reliability in
using as the emergency power in UPS and telephone exchange.
Recommended replacement occasions:
(Determine the replacement period subject to the average ambient
temperature of NP battery application)
NP Battery Temperature Replacement Period
20゛25≧(normal temp.) Within 3 years
30≧ Within 2.5 years
40≧ Within 1.4 years
Don't use (with power-on) the batteries exceeding replacement period,
which may lead to power-out, flame or explosion due to decrease
of content.
(3) Don't put it near to flame or cause shortcut.
(4) Don't decompose. In case of vitriol fro the broken battery
splashing on skin or clothes, flush immediately with clear water.
In case of contact with eyes, flush with clear water before seeing
the doctor.
(5) The battery will lose its function if it gets wet. Don't put
in rain or in water. Don't put it in flame, or it may get broken.
(6) Contact our company for discharge of batteries in quantity.
Don't abandon at random, because they will cause contamination to
our environment.